Need Help?
Oder | Setting Menu | Displayed as | Setting Value | Default |
1 | Wring | “Conn” | 1: 1P2W 2: 1P3W 3: 3P3W-D 4: 3P3W-Y 5: 3P4W | 5 |
2 | PT Ratio | “Pt” | 1.000-1400.0000 | 1 |
3 | CT Ratio | “Ct” | 1-2000(5A), 1-9999 (1A) | 1 |
4 | DEMAND Time | “dE.t” | 1,2,3,4,5,6,10,15,20,30,60 | 15(min) |
5 | Conmunication Address | “Addr” | 1-247 | 1 |
6 | Conmunication Speed | “bPS” | 1: 9600bps 2: 19200bps 3: 38400bps | 3 |
The swap of float variable | S” | On: Yes Off: No | On | |
7 | TX delay time | “tX.t” | 10-200msec | 20(msec) |
8 | IP Address | “tCP” “Adr.” | 1.0.0.0-233.255.255.255 | 192.168.0.100 |
9 | Subnet Mask | “tCP” “Sub.” | 0.0.0.0-233.255.255.255 | 255.255.255.0 |
10 | Gateway | “tCP” “Gat.” | 1.0.0.0-233.255.255.255 | 192.168.0.1 |
11 | Mac address | “C-Ad” | 00-00-00~ FF-FF-FF | – |
12 | TCP idle time | “id.t” | 10-60sec | 10(sec) |
13 | TCP SWAP | “tCP” “S” | On: Yes Off: No | On |
14 | DI1 Debounce time | “dEb” “1” | 10-200msec | 10(msec) |
15 | DI2 Debounce time | “dEb” “2” | 10-200msec | 10(msec) |
16 | RS485 Termination switch | “tEr” | On: Yes Off: No | Off |
17 | Data reset | “rSt” | 0: All Data Reset 1: Wh Reset 2: Varh Reset 3: Vah Reset 4: rWh Reset 5: rVarh Reset 6: Demand A Reset 7: Demand W Reset 8: Max A Reset 9: Max W Reset 10: Max Var Reset 11: Max VA Reset 12: Max V THD Reset 13: Max A THD Reset 14: Max Demand A Reset 15: Max Demand W Reset 16: DI1 Counter Reset 17: DI2 Counter Reset | – |
18 | Led Test | “Led” “tESt” | On: Yes Off: No | Off |
19 | Version display | “vEr.” | XX.XX/X.X | – |