| No. | Function Name | Setting Range | Defaults |
| F00 | Soft start rated current | ||
| F01 | Soft start rated voltage | ||
| F02 | Motor rated current | ||
| F03 | Way to control | 0: Prohibit start and stop 1: The keyboard is individually controlled 2: External control alone control 3: Keyboard + external control 4: Communication is controlled separately 5: Keyboard + communication 6: External control + communication 7: Keyboard + external control + communication | 3: Keyboard + external control |
| F04 | Starting method | 0: Voltage ramp start 1: Current limit start 2: Torque start | 0: Voltge ramp start |
| F05 | Starting current limit percentage | 50% ~ 600% | 300% |
| F06 | Percentage of starting voltage | 30% ~ 80% | 35% |
| F07 | Starting timer | 1s ~ 120s | 15s |
| F08 | Sustain voltage | 60% ~ 85% | 65% |
| F09 | Early acceleration time | 1s ~ 10s | 5s |
| F10 | Hold time | 1s ~ 120s | 10s |
| F11 | After acceleration time | 1s ~ 10s | 3s |
| F12 | Soft stop time | 0s ~ 60s | 0s |
| F13 | Programmable relay 1 | 0: No action 1: Power-on action 2: Soft start action 3: Bypass action 4: Soft stop action 5: Run action 6: Standby action 7: Failure action | 7: Failure action |
| F14 | Relay 1 delay | 0s ~ 600s | 0s |
| F15 | Programming relay 2 (optional) | 0: No action 1: Power-on action 2: Soft start action 3: Bypass action 4: Soft stop action 5: Run action 6: Standby action 7: Failure action | 3: Bypass action |
| F16 | Relay 2 delay | 0s ~ 600s | 0s |
| F17 | 4-20mA upper limit current | 50% ~ 500% | 200% |
| F18 | Motor wiring method | 0: Line type 1: Inner triangle | 0: Line type |
| F19 | Mailing Address | 1 ~ 127 | 1 |
| F20 | Communication baud rate | 0: 2400 1: 4800 2: 9600 3: 19200 | 2:9600 |
| F21 | Operation overload level | 1 ~ 30 | 10 |
| F22 | Starting overcurrent multiple | 50% – 600% | 500% |
| F23 | Start over current protection time | 0s – 120s | 5s |
| F24 | Operating overcurrent multiple | 50% – 600% | 200% |
| F25 | Running overcurrent protection time | 0s – 6000s | 5s |
| F26 | Overvoltage protection multiple | 100% ~ 140% | 120% |
| F27 | Overvoltage protection time | 0s ~ 120s | 5s |
| F28 | Undervoltage protection multiple | 50% – 100% | 80% |
| F29 | Undervoltage protection time | 0s ~ 120s | 5s |
| F30 | Three-phase unbalance | 20% ~ 100% | 40% |
| F31 | Three-phase unbalance protection time | 0s ~ 120s | 10s |
| F32 | Underload protection multiple | 10% ~ 100% | 50% |
| F33 | Underload protection time | 1s ~ 120s | 10s |
| F34 | Soft phase sequence | 0: Any phase sequense 1: Forward sequence 2: Reverse order | 0: Any phase sequence |
| F35 | A phase current calibration value | 10% ~ 1000% | 100% |
| F36 | B phase current calibration value | 10% ~ 1000% | 100% |
| F37 | C phase current calibration value | 10% ~ 1000% | 100% |
| F38 | Voltage calibration value | 10% ~ 1000% | 100% |
| F39 | 4-20mA lower limit calibration | 0% ~ 150.0% | 20.0% |
| F40 | 4-20mA upper limit calibration | 0% ~ 150.0% | 100.0% |
| F41 | Running overload protection | 0: Trip and shutdown 1: neglect | 0: Trip and shutdown |
| F42 | Start overcurrent protection | 0: Trip and shutdown 1: neglect | 0: Trip and shutdown |
| F43 | Running overcurrent protection | 0: Trip and shutdown 1: neglect | 0: Trip and shutdown |
| F44 | Overvoltage protection | 0: Trip and shutdown 1: neglect | 0: Trip and shutdown |
| F45 | Undervoltage protection | 0: Trip and shutdown 1: neglect | 0: Trip and shutdown |
| F46 | Three-phase unbalance protection | 0: Trip and shutdown 1: neglect | 0: Trip and shutdown |
| F47 | Underload protection | 0: Trip and shutdown 1: neglect | 0: Trip and shutdown |
| F48 | Overheating protection | 0: Trip and shutdown 1: neglect | 0: Trip and shutdown |
| F49 | Output phase loss protection | 0: Trip and shutdown 1: neglect | 0: Trip and shutdown |
| F50 | Soft start language | 0: English 1: Chinese | 1: Chinese |
| F51 | Water pump matching selection | 0: None 1: Float 2: Electric contact pressure gauge 3: Water supply level relay 4: Drain level relay | 0: without |
| F52 | Soft start type selection | 0: Online 2: Bypass type | 0: Online |
| F53 | Main control software version | ||
| F54 | Show software version |