Hướng Dẫn Cài Đặt Khởi Động Mềm Sumo SUS-8800

No.Function NameSetting RangeDefaults
F00Soft start rated current  
F01Soft start rated voltage  
F02Motor rated current  
F03Way to control0: Prohibit start and stop
1: The keyboard is individually controlled
2: External control alone control
3: Keyboard + external control
4: Communication is controlled separately
5: Keyboard + communication
6: External control + communication
7: Keyboard + external control + communication
3: Keyboard +
 external control
F04Starting method0: Voltage ramp start
1: Current limit start
2: Torque start
0: Voltge ramp start
F05Starting current limit percentage50% ~ 600%300%
F06Percentage of starting voltage30% ~ 80%35%
F07Starting timer1s ~ 120s15s
F08Sustain voltage60% ~ 85%65%
F09Early acceleration time1s ~ 10s5s
F10Hold time1s ~ 120s10s
F11After acceleration time1s ~ 10s3s
F12Soft stop time0s ~ 60s0s
F13Programmable relay 10: No action
1: Power-on action
2: Soft start action
3: Bypass action
4: Soft stop action
5: Run action
6: Standby action
7: Failure action
7: Failure action
F14Relay 1 delay0s ~ 600s0s
F15Programming relay 2 (optional)0: No action
1: Power-on action
2: Soft start action
3: Bypass action
4: Soft stop action
5: Run action
6: Standby action
7: Failure action
3: Bypass action
F16Relay 2 delay0s ~ 600s0s
F174-20mA upper limit current50% ~ 500%200%
F18Motor wiring method0: Line type
1: Inner triangle
0: Line type
F19Mailing Address1 ~ 1271
F20Communication baud rate0: 2400
1: 4800
2: 9600
3: 19200
2:9600
F21Operation overload level1 ~  3010
F22Starting overcurrent multiple50% –  600%500%
F23Start over current protection time0s –  120s5s
F24Operating overcurrent multiple50% –  600%200%
F25Running overcurrent protection time0s –  6000s5s
F26Overvoltage protection multiple100% ~  140%120%
F27Overvoltage protection time0s ~  120s5s
F28Undervoltage protection multiple50% –  100%80%
F29Undervoltage protection time0s ~  120s5s
F30Three-phase unbalance20% ~  100%40%
F31Three-phase unbalance protection time0s ~  120s10s
F32Underload protection multiple10% ~  100%50%
F33Underload protection time1s ~  120s10s
F34Soft phase sequence0: Any phase sequense
1: Forward sequence
2: Reverse order
0: Any phase sequence
F35A phase current calibration value10% ~ 1000%100%
F36B phase current calibration value10% ~ 1000%100%
F37C phase current calibration value10% ~ 1000%100%
F38Voltage calibration value10% ~ 1000%100%
F394-20mA lower limit calibration0% ~ 150.0%20.0%
F404-20mA upper limit calibration0% ~ 150.0%100.0%
F41Running overload protection0: Trip and shutdown
1: neglect
0: Trip and shutdown
F42Start overcurrent protection0: Trip and shutdown
1: neglect
0: Trip and shutdown
F43Running overcurrent protection0: Trip and shutdown
1: neglect
0: Trip and shutdown
F44Overvoltage protection0: Trip and shutdown
1: neglect
0: Trip and shutdown
F45Undervoltage protection0: Trip and shutdown
1: neglect
0: Trip and shutdown
F46Three-phase unbalance protection0: Trip and shutdown
1: neglect
0: Trip and shutdown
F47Underload protection0: Trip and shutdown
1: neglect
0: Trip and shutdown
F48Overheating protection0: Trip and shutdown
1: neglect
0: Trip and shutdown
F49Output phase loss protection0: Trip and shutdown
1: neglect
0: Trip and shutdown
F50Soft start language0: English
1: Chinese
1: Chinese
F51Water pump matching selection0: None
1: Float
2: Electric contact pressure gauge
3: Water supply level relay
4: Drain level relay
0: without
F52Soft start type selection0: Online
2: Bypass type
0: Online
F53Main control software version  
F54Show software version